8-4. Details of function
¢
Control input function
When function setting is "Operation/Stop" mode 1
Function setting External input Input signal Command
46—00 Terminal
Off → On Operation
On → Off Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
NOTES:
The last command has priority.
The indoor units within the same remote controller group operates in the same mode.
When function setting is "Forced stop" mode
Function setting External input Input signal Command
46—02 Terminal
Off → On Forced stop
On → Off Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
Input
NOTES:
When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 53 -
8-4. Details of function
8. External input and output
DUCT TYPE
ARXG24-45KMLA
DUCT TYPE
ARXG24-45KMLA

Table of Contents

Other manuals for Fujitsu ARXG36KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG36KMLA and is the answer not in the manual?

Fujitsu ARXG36KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG36KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals