1. Specifications
Type
Wall mounted
Inverter heat pump
Model name ASYG07KPCA ASYG09KPCA ASYG12KPCA
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 2.00 2.50 3.40
Btu/h 6,800 8,500 11,600
Min.—Max.
kW 0.9—2.8 0.9—3.0 0.9—3.7
Btu/h 3,100—9,600 3,100—10,200 3,100—12,600
Heating
Rated
kW 2.50 2.80 3.80
Btu/h 8,500 9,500 13,000
Min.—Max.
kW 0.9—3.4 0.9—3.8 0.9—4.80
Btu/h 3,100—11,600 3,100—12,900 3,100—16,400
Input power
Cooling
Rated
kW
0.48 0.71 1.00
Min.—Max. 0.25—1.03 0.25—1.05 0.25—1.14
Heating
Rated 0.63 0.79 1.14
Min.—Max. 0.25—1.39 0.25—1.39 0.25—1.60
Fan
HIGH
W
21.5 26.9
MED 12.5 14.5
LOW 6.3 7.1
QUIET 3.0 3.0
Current
Cooling
Rated A
2.7 3.5 4.7
Heating 3.2 3.8 5.6
EER Cooling
kW/kW
4.17 3.52 3.40
COP Heating 3.97 3.54 3.33
Sensible capacity Cooling kW 1.9 2.1 2.6
Power factor
Cooling
%
77 87 92
Heating 85 90 89
Moisture removal L/h (pints/h) 1.0 (1.8) 1.3 (2.30) 1.8 (3.20)
Maximum operating current *1
Cooling
A
6.5 6.5 6.5
Heating 9.0 9.0 9.0
Fan
Airflow rate
Cooling
HIGH
m
3
/h
580 580 630
MED 460 460 490
LOW 340 340 360
QUIET 240 240 240
Heating
HIGH 580 580 630
MED 460 460 490
LOW 380 380 380
QUIET 260 260 260
Type × Q'ty Cross flow fan × 1
Motor output W 27 27 27
Sound pressure level *2
Cooling
HIGH
dB (A)
45 45 46
MED 38 38 40
LOW 31 31 33
QUIET 22 22 22
Heating
HIGH 45 45 46
MED 40 40 40
LOW 36 36 35
QUIET 26 26 27
Heat exchanger type
Dimensions (H × W × D)
mm
210 × 600 × 26.6
Fin pitch 1.3
Rows × Stages 2 × 10
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
270 × 784 × 224
Gross 279× 864 × 334
Weight
Net
kg
8.0
Gross 11.0
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (1/4)
Gas Ø 9.52 (3/8)
Method Flare
Drain hose
Material PP+HDPE
Size mm Ø 11.8 (I.D.), Ø 15 to Ø 16.8 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 2 -
1. Specifications
WALL MOUNTED