External output
Use an external output cable with appropriate external dimension, depending on the number of
cables to be installed.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to "Combination of external input and output" on page 150.
 When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
 When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected unit Relay
(Operation status)
-
+
- 149 -