13-2. Outdoor unit low noise operation function (option)
Change the outdoor unit low noise operation by using this setting. Optional Central remote
controller is necessary to use this function.
SET2-1 Setting Factory setting
ON Lower
OFF Low ♦
CAUTION
• When the low noise operation function is working, cooling and heating capacity will de-
crease.
• When changing the settings, explain to the customer beforehand that the capacity de-
creases.
13-3. Changing the current limit function
Change the outdoor unit current limit function by using this setting.
SET2-3 SET2-4 Current Factory setting
OFF OFF Full ♦
ON OFF 20.5 A
OFF ON 16.5 A
CAUTION
• When the current limited function is working, cooling and heating capacity will decrease.
• When changing the settings, explain to the customer beforehand that the capacity de-
creases.
DESIGN & TECHNICAL MANUAL
- 328 -
OUTDOOR UNIT
AOYG36LBLA5