11. Safety devices
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Compact
cassette
AUXG07KVLA
250 V, 5 A
Activate: 100 ±15 °C
Fan motor stop
Reset: 95 ±10 °C
Fan motor restart
―
â—‹
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
AUXG18KVLA
AUXG22KVLA
Mini duct
ARXG07KSLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
ARXG18KSLAP
Slim duct
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
Medium static
pressure duct
ARXG22KMLB
Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
―
ARXH22KMTAP
Activate: 115 ±15 °C
Fan motor stop
Reset: 70 °C
Fan motor restart
â—‹
- 183 -
11. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu ASYG14KMTB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG14KMTB and is the answer not in the manual?

Fujitsu ASYG14KMTB Specifications

General IconGeneral
BrandFujitsu
ModelASYG14KMTB
CategoryAir Conditioner
LanguageEnglish

Related product manuals