CHAPTER 5: PRODUCT DESCRIPTION SPECIFICATIONS
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE 5–67
81 UNDERFREQUENCY
Pickup Level:.....................................................20.00 to 70.00 Hz in steps of 0.01
Pickup Accuracy: ............................................±0.02 Hz
Dropout Level:..................................................0.05 Hz
Time Delay: .......................................................0.0 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±100 ms or ±0.5% of total trip time
81 OVERFREQUENCY
Pickup Level:.....................................................20.00 to 70.00 Hz in steps of 0.01
Pickup Accuracy: ............................................±0.02 Hz
Dropout Level:..................................................0.05 Hz
Time Delay: .......................................................0.0-255.0 s in steps of 0.1
Start Delay:........................................................0-5000 s in steps of 1
Timing Accuracy:............................................±100 ms or ±0.5% of total trip time
55 LEAD POWER FACTOR
Pickup Level:.....................................................0.99 to 0.05 in steps of 0.01
Pickup Accuracy: ............................................±0.02
Dropout Level:..................................................0.03 of pickup
Time Delay: .......................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
55 LAG POWER FACTOR
Pickup Level:.....................................................0.99 to 0.05 in steps of 0.01
Pickup Accuracy: ............................................±0.02
Dropout Level:..................................................0.03 of pickup
Time Delay: .......................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
POSITIVE REACTIVE POWER
Pickup Level:.....................................................1 to 25000 in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
NEGATIVE REACTIVE POWER
Pickup Level:.....................................................1 to 25000 kvar in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................96 to 98% of pickup
Time Delay: .......................................................0.1 to 255.0 s in steps of 0.1
Start Delay:........................................................0 to 5000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
37 UNDERPOWER
Pickup Level:.....................................................1 to 25000 kW in steps of 1
Pickup Accuracy: ............................................±2%
Dropout Level:..................................................102 to 104% of pickup
Time Delay: .......................................................0.5 to 255.0 s in steps of 0.5
Start Delay:........................................................0 to 15000 s in steps of 1
Timing Accuracy:............................................±300 ms or ±0.5% of total trip time
REVERSE POWER
Pickup Level:.....................................................1 to 25000 kW in steps of 1
Pickup Accuracy: ............................................±2%