Service Manual
R8010RB
MVAX Page 19/24
3
13
14
R
EXT
(2)
52
T
52-a
C.B. aux.
switch
Trip relay
RL2
Trip coil
27
28
R
EXT
(1)
RL1
3
52-b
C.B. aux.
switch
Trip coil
21
RL2-1
Trip supply (Vx (2))
Alarm supply (Vx (1))
1
RL1-1
42
RL1-2
75
RL1-3
Note:
Contact arrangement shown
is typical only.
Alarm
contacts
P1080ENa
Figure 5: Application diagram – MVAX21 trip circuit supervision relay without preclosing
supervision