EasyManuals Logo
Home>GE>UPS>On-line VH Series

GE On-line VH Series User Manual

GE On-line VH Series
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Critical Power
Modifications reserved Page 11/22
GE_UPS_OPM_VHU_208_2K0_3K0_XUS_V010.docx Operating Manual VH2000-3000 208V UL
3.5 INSTALLATION OF A BATTERY EXTENSION PACK
With a battery extension pack you can increase the battery runtime of the UPS. If you do not install a battery extension
pack please skip this section and proceed with chapter 4.
NOTE
The battery extension packs are suitable if connectable to circuits directly connected to mains and
compliant with the following:
Nominal Voltage (Vdc): 72
Nominal Capacity (Ah): 14
Recharge Current (A): 1.5
The following actions must be performed by qualified and skilled personnel only.
1. Connect the DC connector of the battery pack to the DC socket of the UPS (fig. 3.5.a). You will hear a click when the
cable is properly connected. Block the DC connector: install the small locking plate that came with the battery
pack, and fasten it with the screw provided.
Fig. 3.5.a: Connecting the DC connector
2. Install the first battery pack under the UPS, and position additional packs next to it, according to figure 3.5.b.
Fig. 3.5.b: Connecting the battery packs

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE On-line VH Series and is the answer not in the manual?

GE On-line VH Series Specifications

General IconGeneral
BrandGE
ModelOn-line VH Series
CategoryUPS
LanguageEnglish

Related product manuals