Appendix Table
- 10 -
Appendix Table 3 Hardware Option Function Setting
Block-C parameters (Basic function constants) list
Application
No. Parameter Unit Default Min. Max. Function
ST V/f VEC PM
C02 – Various setting input selection
0
Speed setting input
points selection
4. 1. 4.
=1: Analog fixed
=2: Serial/parallel fixed
=3: Panel fixed
=4: Sequence
O
1
Traverse center
frequency input
points selection
2. 1. 3.
=1: Analog fixed
=2: Panel fixed
=3: Sequence
O
2
Torque setting
input points
selection
3. 1. 4.
=1: Analog fixed
=2: Serial fixed
=3: Panel fixed
=4: Sequence
OO
3
Torque ratio 1
setting input points
selection
2. 1. 3.
=1: Serial fixed
=2: Panel fixed
=3: Sequence
OO
4
Torque bias 1
setting input points
selection
3. 1. 4.
=1: Analog fixed
=2: Serial fixed
=3: Panel fixed
=4: Sequence
OO
5
Torque ratio 2
setting input points
selection
2. 1. 3.
=1: Serial fixed
=2: Panel fixed
=3: Sequence
OO
6
Drive/regenerative
torque limit input
points selection
3. 1. 3.
=1: Analog fixed
=2: Serial fixed
=3: Sequence
OO
7
ASR response
input points
selection
2. 1. 3.
=1: Serial fixed
=2: Panel fixed
=3: Sequence
OO
8
Machine time
constant input
points selection
2. 1. 3.
=1: Serial fixed
=2: Panel fixed
=3: Sequence
OO
Block-C parameters (H/W option function constants) list
Application
No. Parameter Unit Default Min. Max. Function
ST V/f VEC PM
C32 – PC (parallel) Interface
0
Input mode
(strobe)
1. 1. 3.
=1: 16-bit strobe
=2: 8-bit time multiplexed strobe
=3: 16-bit sample
O
1
Input mode (input
logic)
1. 1. 2.
=1: 1 at closed circuit
=2: 1 at opened circuit
O
2 Data format 1. 0. 10.
Set according to the following
table.
O
Setting data Format Setting resolution Setting range
0
1
2
3
16-bit binary
16-bit binary
16-bit binary
16-bit binary
0.01Hz/LSB (0.1rpm/LSB)
0.1Hz/LSB ( 1rpm/LSB)
0.01%LSB
0.1%LSB
0 to 440.00Hz (0.0 to 6553.5rpm or Nmax)
440.0Hz (0 to Nmax rpm)
100.00%
100.0%
4
5
6
7
16-bit BCD
16-bit BCD
16-bit BCD
16-bit BCD
0.01Hz/LSB (0.1rpm/LSB)
0.1Hz/LSB ( 1rpm/LSB)
0.01%LSB
0.1%LSB
99.99Hz (0.0 to 999.9rpm)
100.0Hz (0 to Nmax rpm)
99.99%
100.0%
8
9
10
8-bit binary
12-bit binary
16-bit binary
1/255%
1/4095%
1/65535%
100.0%
100.0%
100.0%
Hz = Frequency setting [ For V/f control (Constant torque, reduced torque) (C30-0 = 1, 2) ]
rpm: Speed setting
For IM speed sensorless vector control (C30-0 = 3)
For IM speed vector control (C30-0 = 4)
For PM motor control (C30-0 = 5)
Set this when the Parallel interface option (U2KV23PL0) has been mounted.