650 1250 1350
OPERATOR INTERFACE
DISPLAY
Type LCD sfondo nero
Screen area (L x H) 35 x 30 mm 37x 68 mm 83x68 mm
Lighting Backlit with LEDs, life > 40,000 hours @ 25 °C
PV display
Number of digits: 4 to 7 segments, with decimal point
Digit height: 17 mm; Color: white or “custom”
Number of digits: 4 to 7 segments,
with decimal point. Digit height: 23
mm; Color: white or “custom”
SV display
Number of digits: 5 to 14 segments,
with decimal point. Digit height:
7.5 mm; Color: green or “custom”
Number of digits: 4 to 7 segments,
with decimal point. Digit height: 14
mm; Color: green or “custom”
Number of digits: 4 to 7 segments,
with decimal point. Digit height: 11
mm; Color: green or “custom”
F display
Number of digits: 5 to 14 segments,
with decimal point. Digit height: 9
mm; Color: amber or “custom”
Number of digits: 7 to 14 segments,
with decimal point. Digit height: 9
mm; Color: amber or “custom”
Unit of measurement Selectable, °C, °F or custom 1; Color: same as PV display
Controller state signals Number: 6 (RUN, MAN, _/-, REM, SP1/2), Color: amber
Output state signals
Number: 4 (1, 2, 3, 4)
Color: red
Bargraph indicator,
configurable
Type: graphic bargraph,11 segments
Power indication: 0...100% or -100...100%
Current indication: 0...100% f.s.
Valve position indication: 0...100%
KEYPAD
Number of keys: 4 silicon (Man/Auto, INC, DEC, F), Type: mechanical
Number of keys: 6 silicon
( Man/Auto, L/R,*, INC, DEC, F)
INPUTS
MAIN INPUT
Sensor type TC, RTD (PT100, JPT100), IR ES1B, DC linear sensor
Accuracy
TC inputs:
Calibration accuracy: < +/- (0,25% of reading value in °C +0,1°C)
Linearization accuracy: 0,1% of reading value
Cold junction accuracy: < +/- 1,5°C a 25°C room temperature)
Cold junction compensation: > 30:1 rejection to the change of the room temperature
RTD input:
Calibration accuracy: < +/- (0,15% of reading value in °C +0,4°C)
Temperature drift: < +/- (0,005% of reading value in °C +0,015°C )/°C from 25°C room temperature
Linearization accuracy: 0,1% of reading value
Linear inputs:
Calibration accuracy< 0,1% full scale
Temperature drift: < +/- 0,005% full scale /°C at 25°C room temperature
Sampling time 60 ms / 120 ms, selectable
Digital filter 0,0...20,0 s
Temperature unit of
measurement
Degrees C / F, selectable from keypad
Signal interval
Type: linear
Scale: -1999...9999, settable decimal point
TC (thermocouple) input Thermocouple: J, K, R, S, T, C, D; Linearization: ITS90 or custom;
RTD (resistance
thermometer) input
Resistance thermometer: PT100, JPT100; Input impedance (Ri): ≥ 30 kΩ;
Linearization: DIN 43760 or custom; Max. line resistance: 20 Ω
DC linear input
0...60 mV input impedance (Ri): > 70 kΩ
0...1 V input impedance (Ri): > 15 kΩ
0...5 V / 0...10 V input impedance (Ri): > 30 kΩ
0/4...20 mA input impedance (Ri): 50 Ω
Linearization: linear or custom
AUXILIARY
INPUT
Remote setpoint 0...1 V, 0...10 V, 0/4...20 mA
Scale
0...1 V input impedance (Ri): > 15 kΩ
0...10 V input impedance (Ri): > 10 kΩ
0/4...20 mA input impedance (Ri): 50 Ω
Accuracy 0,1% f.s. ±1 digit @25 °C
CT INPUT
(ammeter)
Type Isolated via external transformer
Number: 2 max - Max. capacity: x / 50 mA AC - Line frequency: 50/60 Hz - Input impedance (Ri): 10 Ω
Accuracy ±2% f.s. ±1 digit @25 °C
DIGITAL
INPUTS
Number 3 max 5 max
Type voltage-free contact, or NPN 24 V - 4,5 mA, or PNP 12/24 V - max 3,6 mA.
Isolation 500 V
OUTPUTS
ALARMS
Relay
(R)
Number: 4 max
Type of relay contact: NO
Max. current: 5 A, 250 VAC / 30 VDC,
Number: 4 max
Type of relay contact: NO
Max. current: 5 A, 250 VAC / 30 VDC, cosφ = 1
Minimum load: 5 V, 10 mA - Life cycle: > 100.000 operations - Double isolation
Logic (D) Number: 2 max - Type: for solid-state relays - Voltage: 24 V ±10% (min 10 V @20 mA) - Isolated from main input
Triac ( long life relè)
(T)
Number: 1 max
Load: resistive
Voltage: 75...264 VAC
Current max: 1 A
Isolation 3 kV;
snubber circuit integrated
zero crossing switching
Number: 1 max
Load: resistive
Voltage: 12...240 VAC
Current max: 2 A
Isolation 2,5 kV
zero crossing switching