5 Installation
5.1 Installation Requirements
1. Do not install the equipment in a place near ammable, explosive, or corrosive materials.
2. Install the equipment on a surface that is solid enough to bear the inverter weight.
3. Install the equipment in a well-ventilated place to ensure good dissipation. Also, the
installation space should be large enough for operations.
4. The equipment with a high ingress protection rating can be installed indoors or outdoors.
The temperature and humidity at the installation site should be within the appropriate range.
5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
6. Do not install the equipment in a place that is easy to touch, especially within children’s
reach. High temperature exists when the equipment is working. Do not touch the surface to
avoid burning.
7. Install the equipment at a height that is convenient for operation and maintenance, electrical
connections, and checking indicators and labels.
8. The installation place of the inverter shall be far away from the living areas considering that
the vibration it has may bother the residents during its working.
9. Install the inverter away from high magnetic eld to avoid electromagnetic interference.If
there is any radio or wireless communication equipment below 30MHz near the inverter, you
have to:
• Install the inverter at least 30m far away from the wireless equipment.
• Add a low pass EMI lter or a multi winding ferrite core to the DC input cable or AC output
cable of the inverter.
Installation Environment Requirements
Children No Touch
≥600mm
≥1000mm
≥600mm
≥50mm
≥600mm
≥600mm