Multi Variable Air Conditioners Ducted Type Indoor Unit
13
4.4 Installation of Air Duct
Caution:
There should be insulating layer on air-out duct, air-return duct and fresh air duct to avoid
heat loss and moisture. Adhere a nail on the air duct and then add thermal sponge with a
layer of tin. Fasten it with a nail cover and then seal the junction with tin tapes; you can
also use other materials that have good insulation quality.
Each air-out duct and air-return duct should be fixed on a pre-made board with iron frame.
The junction of air duct should be well-sealed in order to prevent air leakage.
The design and construction of air duct should comply with national requirements.
The edge of air-return duct is suggested to be more than 150mm away from the wall. Add
a filter to the air-return opening.
Please consider noise-damping and vibration damping for the design and construction of
air duct. Besides, noise source must be away from people. For instance, do not have the
air-return opening installed on top of the user (offices, rest area, etc.).
4.4.1 Installation of Air-out Duct
(1) Duct Shape and Size of Air Outlet and Air-return Opening
Fig 4.4.1 Air Outlet
Fig 4.4.2 Air-return Opening