GMV5 Home DC Inverter Multi VRF Units
277
value).
2.2The
fluid pipe
is
blocked.
Touch the pipe
along the
flowing
direction of
refrigerant to
feel the
temperature
difference. The
difference is
large or part of
the pipe is
frosting.
Replace
and solder
the pipe.
2.4The
pipe that
connects
the IDU is
blocked.
Touch the pipe
along the
flowing
direction of
refrigerant to
feel the
temperature
difference. The
difference is
large or part of
the pipe is
frosting.
2.4.1The
block is
caused
by solder.
Cut off the
pipe and
check it.
Replace
and solder
the pipe.
2.4.2The
pipeline
is
blocked
by
impurities
.
Replace
and solder
the pipe.
3.The
ambient
temperatu
re is too
high.
3.150In
the
cooling
mode, the
outdoor
temperatu
re is over
50C.
Measure the
outdoor
ambient
temperature.
It is a
normal
phenomen
on caused
by the
protection
function.
3.2In the
heating
mode, the
actual
ambient
temperatu
re of the
IDU's
return air
is over
30C.
Measure the
outdoor
ambient
temperature.
It is a
normal
phenomen
on caused
by the
protection
function.