GMV5 Home DC Inverter Multi VRF Units
67
Fig.3.2 Parts of Wired Controller
Panel of wired
controller
Soleplate of wired
controller
Wiring box
mounted in the
wall
3.3.1 Installation of Wired Controller
3.3.1.1 Selection of Communication Wire
Fig.3.3 Length of Communication Wire
Total length of
communication
wire between
indoor unit and
wired
controller L(m)
Light/Ordinary
polyvinyl chloride
sheathed twisted
copper cord (RVVS)
Total length of
communication wire
can’t exceed 250m.
Shielding
light/Ordinary
polyvinyl chloride
sheathed twisted
copper cord (RVVSP)
If unit is installed in a
place with strong
electromagnetic
interference, use
shielding wire (RVVSP)
as the communication
wire of the wired
controller.
Notice:
â‘ If air conditioner is installed in a place with strong electromagnetic interference,
communication wire of wired controller must be shielding twisted pair.