EasyManuals Logo

Gree SXVD300LCJ2/A-K User Manual

Gree SXVD300LCJ2/A-K
391 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #324 background imageLoading...
Page #324 background image
GMV5 Home DC Inverter Multi VRF Units
318
2. Remove the
electric box.
●Disconnect internal and external
connecting wires of the electric
box.
●Protect the internal parts during
the disassembly.
3. Disassemble the
electric expansion
valve.
●Remove the coil from the electric
expansion valve;
Heat up the connecting pipes of
the electric expansion valve with
welding and then remove the
pipes.
Note: Prevent nearby parts from
being burnt during welding.
4. Remove the
electric expansion
valve.
Remove the electric expansion
valve.
5. Install a new
electric expansion
valve.
Weld the connecting pipes of the
electric expansion valve.
Before welding, cover the valve
with wet cloth.
During welding, charge nitrogen
into the pipes. The pressure
should be controlled within 0.5±0.1
kgf/cm2 (relative pressure).
Note: Prevent nearby parts from
being burnt during welding.
Install the coil on the electric
expansion valve.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree SXVD300LCJ2/A-K and is the answer not in the manual?

Gree SXVD300LCJ2/A-K Specifications

General IconGeneral
BrandGree
ModelSXVD300LCJ2/A-K
CategoryInverter
LanguageEnglish

Related product manuals