HVLS Touchscreen Control 9
®
The following communication point lists apply to touchscreen control installations that were provided with optional
BACnet MSTP communication for building management system (BMS) integration. BACnet points must be
programmed into the building’s BMS (by others) for proper communication between BMS and the touchscreen
control.
NOTE: X denotes Modbus address values between 2-31 that are set via dipswitches on the fan’s variable frequency
drive circuit board.
HVLS Fan Points
Type Instance Variable Name Read/Write DataType Description
AnalogInput 0 MS_ToBACnet.BN_NumberOfFans Read Only Real Total number of fans in the system
BinaryInput X Fan[X].Enabled Read Only Bool Fan at Modbus address [X] found in system
BinaryValue X01 BMSFanOffOn[X] Read/Write Bool
BMS Off/On command for fan at Modbus
address [X]
BinaryValue X02 Fan[X].Override Read/Write Bool Fan at Modbus address [X] override command
BinaryInput X03 FanCommand.OverrideStatus[X] Read Only Bool
Local override for fan at Modbus address
[X] enabled
AnalogValue X04 BN_LightSet[X] Read/Write Real Percentage light for fan at Modbus address [X]
MultiStateInput X05
MS_ToBACnet.BN_
RunCommand[X]
Read Only UInt
OFF; COOLING; HEATING - Status of fan at
Modbus address [X]
AnalogInput X06 MS_ToBACnet.BN_SpeedRefSet[X] Read Only Real Fan at Modbus address [X] speed
MultiStateInput X07 MS_ToBACnet.BN_OpStatus[X] Read Only UInt
OK; CRC ERROR; DRIVE FAULT; MOTOR TEMP
WARNING; IGBT TEMP WARNING; FIRE INPUT;
WIND SHUT DOWN - Hardware status of fan at
Modbus address [X]
AnalogInput X08
MS_ToBACnet.BN_
GroupNumber[X]
Read Only Real Fan at Modbus address [X] group number
AnalogInput X09
MS_ToBACnet.BN_
ScheduleNumber[X]
Read Only Real Fan at Modbus address [X] schedule number
MultiStateInput X10 MS_ToBACnet.BN_Fault[X] Read Only UInt
NO FAULT; MODBUS TIMEOUT; IMPACT
DETECTION; MOTOR OVER TEMP; DRIVE OVER
TEMP; BUS OVER VOLT; BUS UNDER VOLT;
PHASE OVER CURRENT; MCU HIGH TEMP;
OVERSPEED - Drive status of fan at Modbus
address [X]
BinaryValue X11 Fan[X].ForwardReverse Read/Write Bool
Forward/Reverse command for fan at Modbus
address [X]
Optional Temp/Humidity Sensor Points
Type Instance Variable Name Read/Write DataType Description
BinaryValue 0 SummerWinterMode Read/Write Bool
Summer or winter mode for temp/humidity
operation
AnalogInput 1 RoomTemp.Val Read Only Real Temperature in C
AnalogInput 2 RoomRH.Val Read Only Real Percentage RH
AnalogInput 3 CeilingTemp.Val Read Only Real Temperature in C
AnalogInput 4 CeilingRH.Val Read Only Real Percentage RH
EXAMPLE: Below is an example of BACnet addressing for the fan at address 29
Type Instance Variable Name Read/Write DataType Description
MultiStateInput 2905
MS_ToBACnet.BN_
RunCommand[29]
Read Only UInt
OFF; COOLING; HEATING - Status of fan at
Modbus address [29]
BACnet MSTP Communication Points (Optional)