1U09BE5ERA
1U12BE5ERA
1U18EE5ERA
1U24GE5ERA
45
1U09BN2ERA
1U12BN2ERA
1U18EN2ERA
1U09BE5ERA
1U12BE5ERA
1U18EE5ERA
9.52x0.8mm
15.88x1.0mm
1U24GE5ERA
1.
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
ƽ
andthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.ƽ
Half union
Flare nut
Torque wrench
CAUTION
Be careful that matters, such as wastes of sand
s,water,
,etc.shallnotenterthepipe.
ThestandardpipelengthisC m.IfitisoverDm,thefunctionoftheunitwillbeaffected.Ifthepipe
has
to be lengthened, the refrigerant should be charged,
accordingtoEg/m.Butthechargeofrefrigerant
must
be conducted by profes
sional air conditioner engineer. Before adding additional refrigerant,
perform
air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ)Fasteningtorque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
Max.Elevation:
●
In case the elevation A is more
●
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
●
Incasethepipelength B is●
more thanDm, the refrigerant
should be charged, according
to E g/m.
Connection of pipes
charge
additional refrigerant.
Amax
Bmax
2.