262
Super Match
6. Limitation values on pipe installation
3U19FS1ERA 3U19FS1ERA(N) 3U24GS1ERA 3U24GS1ERA(N)
Item Unit Description Standard Maximum
A,B,C liquid pipe mm Size of the liquid side connection pipe φ6.35 /
A,B,C Gas pipe mm Size of the gas side connection pipe φ9.52 /
L1 (one way) m Max.piping length between IU and OU of the way
10 25
L2 (one way) m Max.piping length between IU and OU of the way
10 25
L3 (one way) m Max.piping length between IU and OU of the way
10 25
L1+L2+L3 m Total liquid piping length
30
3U19: 50
3U24: 60
m
Drop between every two indoor units when the location of
the outdoor unit is among indoor units
1 15
m
Drop between every two indoor units when the location of
the outdoor unit is at one side of indoor units
1 7.5
H+ m Drop between the outdoor unit and the indoor unit
5 15
m
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is among the indoor units
5 7.5
m
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is at one side of indoor units
5 15
h
H-
The piping length information, please refer the following table.

Other manuals for Haier 1U60IS1ERB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier 1U60IS1ERB and is the answer not in the manual?

Haier 1U60IS1ERB Specifications

General IconGeneral
BrandHaier
Model1U60IS1ERB
CategoryAir Conditioner
LanguageEnglish

Related product manuals