Electic Control and
Debugging
343
Super Match
Wiring controller communication address: for PCB 0151800106 and 0151800106A,the dip switch is SW2,; for
0151800175B , the dip switch is SW3.:
Wiring controller
address
SW2-1 SW2-2 SW2-3 SW2--4
Master unit 0 0 0 0
Slave unit 1 1 0 0 0
Slave unit 2 0 1 0 0
Slave unit 3 1 1 0 0
----- ----- ----- ----- -----
Slave unit 15 1 1 1 1
In single split system
,
when the wired controller control more than 1 units, please set the indoor unit address by
adjusting the PCB DIP switch SW2 as above.In MAXI split system
,
no need to set the indoor unit address, just
keep the factory setting
(
SW2 :OFF/OFF/OFF/OF).
AD48NS1ERA(S) AP48DS1ERA(S)
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
1 1 0 --- --- --- --- --- 48K indoor unit
1 1 0 --- --- --- --- --- 48K indoor unit
--- --- --- 0 --- --- --- --- Room card unavailable(default)
--- --- --- 1 --- --- --- --- Room card available
--- --- --- --- 0 --- --- --- heating pump
(
default
)
--- --- --- --- 1 --- --- --- cooling only
--- --- --- --- --- 0 1 0 AD48NS1ERA
--- --- --- --- --- 0 0 1 AP48DS1ERA
Note:
Static pressure value for AD09~24SS1ERA,AD09~24SS1ERA(N),AD09~24SS1ERA(N)(P), AD12/18/MS1ERA and
AD12/18/MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) (selection by SW1-4 SW1-5 )
Static pressure(Pa) 1st 2nd 3rd 4th
AD**SS1ERA 0 10 20 30
AD**SS1ERA(N) 0 10 20 30
AD**SS1ERA(N)(P) 0 10 20 30
AD12MS1ERA
AD18MS1ERA
AD12MS1ERA(D)
AD18MS1ERA(D)
AD24MS2ERA
AD24MS2ERA(D)
AD28MS2ERA(S)
AD28MS2ERA(S)
10 30 50 70
10 30 50 70
10 30 50 70
10 30 50 70
10 30 50 70
10 30 50 70
(