EasyManuals Logo

Haier 2U14CS1ERA User Manual

Haier 2U14CS1ERA
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
48
Domestic air conditioner
6
2U14CS1ERA-SM
Introduction
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe has already existed.
2.Pulloutthecableonthefrontside,andconnectthecable
making a loop.
When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not
becarriedoutandwillcausedefect.
Insertthecablefromtheback
ƽ
side of the unit, then pull it out
on the front side.
Loosen the screws and insert
ƽ
the cable ends fully into
terminal block, then
tighten the screws.
Pull the cable slightly to
ƽ
make sure the cables have
been properly inserted and
tightened.
After the cable connection,
ƽ
never fail to fasten the connected cable with the
wiring cover.
When connecting the cable after installing the indoor unit
When connecting the cable before installing the indoor unit
Note:
1.Ifthesupplycordisdamaged,itmustbereplacedbythemanufacturerorits
service agent or a similar qualified person. The type of connecting wire is
H05RN-F
or H07RN-F.
2. If the fuse on PC board is broken please change it with the
type of
3.Thewiringmethodshouldbeinlinewiththelocalwiringstandard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into xed wiring. The breaker should be
all-pole
switch and the distance between its two c
ontacts should be not less
than 3mm.
T.3.15A/250VAC (Indoor).
To Outdoor unit
Model
Connecting wiring
4G0.75mm
2
4G0.75mm
2
4G0.75mm
2
AS07GS2ERA
AS09GS2ERA
AS12GS2ERA
AS18GS2ERA
AS24GS2ERA
The power source must be exclusively used for air
ƽ
conditioner.
In the case of installing an air conditioner in a moist place,
ƽ
please install
an ea
For installation in other places, use a circuit breaker as far
ƽ
as possible.
Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, aring work is carried out.
PowerSourceInstallation
CuttingandFlaringWorkofPiping
FlaretoolforR410A Conventionalflaretool
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
rth leakage breaker.
Lean
Damage of flare Partial Too outside
Correct Incorrect
On Drainage
It becomes
high midway.
The gap with the
ground is too small.
There is the bad
smell from a ditch
It waves.
The end is imm-
ersed in water.
Pleaseinstallthedrainhosesoastobedownwardslopewithoutfail.
Please don’t do the drainage as shown below.
ƽ
ƽ
Please pour water in the drain pan of the indoor unit, and
ƽ
is carried out surely to outdoor.
In case that the attached drain hose is in a room, please
ƽ
apply heat
insulation
to
Less than
5cm
confirm that
drainage
it without fail.
Crack
Indoor unit
Check Items for Test Run
Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of indoor and outdoor rmly
Is the connecting wiring of indoor and outdoor firmly fixed?
Is drainage securely carried out?
Is the earth line securely connected?
Istheindoorunitsecurelyfixed?
Is power source voltage abided by the code?
Is there any noise?
Is the lamp normally lighting?
Arecoolingandheating(wheninheatpump)performednormally?
Is the operation of room temperature regulator normal?
Please kindly explain to our customers how to
operate
throughtheinstructionmanual.
inserted to the terminal block?
Ƶ
Put check mark
in boxes
Code
indication
Trouble description Analyze and diagnose
E1
Indoor fan motor
malfunction
E2
Heat-exchange
sensor failure
E4
Indoor EEPR OM
erro r
Faulty EEPROM data;
Faulty EEPROM;
Fault
y
PCB;
E7
Comm unication
fault between
indoor and outdoor
units
Indoor unit- outdoor unit signal
transmission error due to wiring
erro r;
Faulty PCB;
E14
In do o r fa n mo to r
malfunction
Operation halt due to breaking
of wire inside the fan m otor;
Operation halt due to breaking
of the fan motor lead wires;
Detectionerrorduetofaulty
indoor unit PCB;
Faulty connector connection;
Faulty therm istor;
Faulty PCB;
Flare tooling die
1.Cut pipe
2.Remove burs
3.Insert the flare nut
4.Flare pipe
ƽ
ƽ
On Drainage
Check for Installation and Test Run

Other manuals for Haier 2U14CS1ERA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier 2U14CS1ERA and is the answer not in the manual?

Haier 2U14CS1ERA Specifications

General IconGeneral
BrandHaier
Model2U14CS1ERA
CategoryAir Conditioner
LanguageEnglish

Related product manuals