14
PP38+ Pellet Stove
Through the ceiling vent, follow PL vent manufacturers
recommendations when using wall and ceiling pass
through.
Fig. 14
PL vent manufacturer's
restop spacer and
support
(See Page 7 for
corner installation
clearances)
It is required that outside air
be installed with this venting
conguration to reduce smoke
and creosote smell in the room
in the event of power failure.
Min. above ground level
18"
Storm collar
Flashing
3" min.
3" min.
12" min.
3" min.
Fig. 15
3" min.
No insulation or
other combustible
materials are
allowed within
3" of the pellet
vent pipe. Unless
specied by the
pipe manufacturer
12" min. wall to outlet
36" min clearance to any
combustible material
Fig. 16