Barrier Gate User Manual
21
Stop + Rise + Fall: Press them to switch between hall limit position and angle sensor limit
position. If angle sensor limit position is applied, the boom pole has resistance rebound
function.
7.2 Dip Switch Description
The dip switch is shown as below. There are four levels of the switch.
Figure 7-2 Dip Switch
S0: If it is on, counting function is enabled. If it is off, the counting function is disabled.
S1: In angle sensor mode, switch it to switch the limit position learning modes. If it is on, it will
switch to auto learning mode. If it is off, it will switch to manual learning mode.
S2: If it is on, the barrier gate will continuously output signal during the rising/falling of the
boom pole. If it is off, the barrier gate will output signal after it is at the rising/falling limit
position.
S3: If it is on, delayed boom pole falling is enabled. If it is off, delayed boom pole falling is
disabled.
7.3 Limit Position Learning Mode Description
Manual learning mode: To locate the rising and falling limit positions manually and accurately.
Auto learning mode: To locate the current position as the rising limit position (or falling limit
position), locate the falling limit position (or rising limit position) automatically, and judge the
boom pole direction.
The barrier gate must be switched to manual learning mode after leaving factory.
7.4 Status Indicator Description
Normal working status:
– When you adopt angle sensor limit position, the status indicator will flash in the frequency
of 0.5 s. When you adopt hall limit position, the status indicator will be solid.
– When the delayed boom pole falling is enabled, the status indicator will flash in the