X‑COM 01 E 3 Product Description
HI 801 566 E Rev. 13.00.00 Page 19 of 46
3.5.11 System Bus Indicators
The system bus indicator LEDs are labeled Sys Bus.
LED
Color
Status
Description
A
Green
On
Physical and logical connection to the system bus
module in slot 1.
Blinking1
No physical connection to the system bus module in
slot 1.
Yellow
Blinking1
The physical connection to the system bus module in
slot 1 has been established.
No connection to a (redundant) processor module
running in system operation.
B
Green
On
Physical and logical connection to the system bus
module in slot 2.
Blinking1
No physical connection to the system bus module in
slot 2.
Yellow
Blinking1
The physical connection to the system bus module in
slot 2 has been established.
No connection to a (redundant) processor module
running in system operation.
A+B
Off
Off
Neither physical nor logical connection to the system
bus modules in slot 1 and slot 2.
Table 9: System Bus Indicators
3.5.12 Fieldbus and Automation Network Indicators
The LEDs of the fieldbus and automation network indicators are labeled FB/AN.
LED
Color
Status
Description
1
Green
On
The meaning depends on the automation network
protocol.
Blinking-x
The meaning depends on the automation network
protocol.
Yellow
On
The meaning depends on the automation network
protocol.
Off
The automation network protocol is not active!
The COM is in the STOP state.
2
Green
On
The meaning depends on the fieldbus protocol.
Blinking-x
The meaning depends on the fieldbus protocol.
Yellow
On
The emergency loader is active.
Off
The fieldbus protocol is not active!
The COM is in the STOP state.
Fault
Red
Blinking1
Fieldbus fault of the bus (e.g., the slave is not present
or faulty response), depending on the fieldbus protocol
(minimum blinking duration 5 s).
Off
No fieldbus fault.
Table 10: Fieldbus and Automation Network Indicators

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HIMA HIMax X-COM 01 E and is the answer not in the manual?

HIMA HIMax X-COM 01 E Specifications

General IconGeneral
BrandHIMA
ModelHIMax X-COM 01 E
CategoryControl Unit
LanguageEnglish

Related product manuals