6.3 Compressor
Input voltage/frequency:220-240V/50Hz
Imput power:≤64.2*115% W
6.3.1 Basic parameters
6.3.2 Checking method
6.Circuit and checking
1.Compressor will start 10 seconds after power-on,if it starts
unsuccessfully,remove the electric box cover and check.
2.Check the connecting wiring between compressor and mainboard
and repair if it is broken.
3.Use a multimeter to measure voltage between N label and COMP
label on CN2 connector of mainboard,then measure frequency of CN8
connector.If the voltage equal to electric supply power and there is
stabilized frequency,it means the compressor is broken,change it;
If not,change the mainboard.