3
CONNECTION KIT SELECTION
PIPING WORK AND REFRIGERANT CHARGE
3.1 Connecon kit selecon
! CAUTION
When brazing pipes, always protect the surrounding elements of the working area in order to avoid
damage due to the high temperature of the ame.
The oponal piping connecon kit is required for the combinaon unit.
Operaon mode Outdoor unit
Connecon kit
Heat pump system
air365 Max
26 - 48 2 MC-21AN1
50 - 54 3 MC-30AN1
56 - 72 3 MC-NP31SA
74 - 96 4 MC-NP40SA
air365
Max Pro
20 - 24 2 MC-20AN1
26 - 36 2 MC-21AN1
38 - 54 3 MC-30AN1
Heat recovery system
air365
Max
26 - 48 2 MC-21XN1
50 - 54 3 MC-30XN1
air365
Max Pro
20 - 24 2 MC-20XN1
26 - 36 2 MC-21XN1
38 - 54 3 MC-30XN1
3.2 Pipe size selecon
Select the pipe size in line with the following instrucons:
Between the outdoor unit and the branch pipe (mul-kit): select the same pipe connecon size as
for the outdoor unit.
Between the branch pipe (mul-kit) and the indoor unit: select the same pipe connecon size as
for the indoor unit.
! CAUTION
• Do not use refrigerant pipe sizes other than those indicated in the technical informaon. The
diameter of the refrigerant pipes depends directly on the power of the outdoor unit.
• If larger diameter refrigerant pipes are used, the circuit lubricaon oil tends to separate from
the gas carrying it. The compressor will be seriously damaged due to a lack of lubricaon.
• If smaller diameter refrigerant pipes are used, the gas or liquid refrigerant will have serious
dicules in circulang. System performance will be aected. The compressor will run under
more severe condions than foreseen and will be damaged in a short space of me.
• The copper pipe used in the refrigeraon installaons is dierent to the copper pipe used in
installaons carrying domesc or heang water.