“A” Group: Standard Functions
Configuring Drive
Parameters
3–10
NOTE: The base frequency must be less than or equal to the maximum frequency (ensure that
A003 A004).
A203 Base frequency setting,
2nd motor
Settable from 30 Hz to the
maximum frequency
✘ ✘ 50. 60. 60. Hz
>A203 2F-BASE
F 0060Hz
A303 Base frequency setting,
3rd motor
Settable from 30 Hz to the
maximum frequency
✘ ✘ 50. 60. 60. Hz
>A303 3F-BASE
F 0060Hz
A004 Maximum frequency
setting
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A004 F-max
F 0060Hz
A204 Maximum frequency
setting, 2nd motor
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A204 2F-max
F 0060Hz
A304 Maximum frequency
setting, 3rd motor
Settable from 30 Hz to
400 Hz
✘ ✘ 50. 60. 60. Hz
>A304 3F-max
F 0060Hz
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE
(EU)
–FU
(US)
–FR
(JP)

Table of Contents

Other manuals for Hitachi SJ300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi SJ300 Series and is the answer not in the manual?

Hitachi SJ300 Series Specifications

General IconGeneral
BrandHitachi
ModelSJ300 Series
CategoryInverter
LanguageEnglish

Related product manuals