Installation Instructions MB-Secure 1000/2000/3000/4000/5000/6000 31
3.11 Special notes on installation and planning
Software version IDENT-KEY evaluation unit 023312.10 / door controller module for MB 023350
To operate a IDENT-KEY IK3 evaluation unit or a access control BUS-2 door module in conjunction with the
MB-Secure control panel, the evaluation unit or door controller module must compulsorily be at software version
V12 or higher.
Software versions for "Centralized Authorization " mode (number of IDENT-KEY ID data carriers >1024)
When "Centralized Authorization " mode is used, software version V13 or higher is mandatory for the BUS-2
user IDENT-KEY IK3 evaluation unit and Door controller module. BUS-2 user Doorguard must be configured
with software version V03.04 or higher.
Transmission devices
The transmission devices must be at
adjacent firmware versions.
DS 6700 / DS 6750
from V07
DS 7700
from V09
Systems in VdS Class C must be operated with an integrated transmission device.
The transmission device must be located inside the control panel and installed with it.
Remote queries of the DSxx are not allowed according to VdS.
The connection between the control panel and the transmission device is made via the serial interface
or via relay. When using the DSxx, we recommend the serial interface. When using another
transmission device, the absence of feedback must be guaranteed. Additional relay assemblies may
have to be installed.
BUS-2 operating units
A maximum of 10 operating units can be connected to each BUS-2 Controller.
Firmware
In principle, the latest firmware for individual users in each case must be used so that all new functional
enhancements can be utilized. Firmware updates are device-dependent. You can find the relevant information
in the documentation of the respective device.
IB2 users
- Up to 10 IB2 users per BUS branch
- Maximum of 10 interface modules 013930 per control panel
- Maximum of 40 I/O modules 013940 per control panel
Module / Parameter
max. per
MB-Secure
max. per
BUS-2 branch
max. per
IB2-branch
IB2 branch
4
-
-
IB2 user
40
-
10
BUS-2 branch
43
-
-
BUS-2 user
1200
64
-
013930 IB2 1to4 Bus expansion
10
-
10
TouchCenter Tuxedo (013002ff)
50
10
-
RF user
256
-
-
RF panic button
32
-
-
IB2 Bus expansion
When using the MB-Secure control
panel in combination with the IB2
bus expansion, the following
firmware versions are mandatory:
MB-Secure
IB2 bus expansion
up to V04.07
up to V01.12
from V04.08
from V01.14

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell MB-Secure 3000 and is the answer not in the manual?

Honeywell MB-Secure 3000 Specifications

General IconGeneral
BrandHoneywell
ModelMB-Secure 3000
CategoryControl Panel
LanguageEnglish

Related product manuals