XIO FAMILY OF SPECTRUM SYSTEM REMOTE INPUT/OUTPUT DEVICES
11 31-00360—01
Replacement of Spectrum Rack Output Module (ROM)
Replacement of one legacy Novar Spectrum ROM module requires installation of up to two XIO-ROM-S modules. Each
new module must be assigned its own unique address for communication within the allocated range for the ROM.
Replacement of Spectrum Compressor Output Module (COM)
Replacement of one legacy Novar Spectrum COM module requires installation of up to two XIO-COM-S-H modules. Each
new module must be assigned its own unique address for communication within the range allocated for the COM.
Table 9. Product Comparison (ROM).
Product Family: Novar Spectrum XIO Spectrum
Module Name: ROM XIO-ROM-S
Outputs: 16 relay outputs
Form-C
8 relay outputs
Form-C
Address Range: 32 to 39 (8 available)
Set address jumpers A2, A1 & A0
32 to 39 (8 available)
Set Module Config switches 1, 2 & 3
Application Programming: Application programming can
have links to outputs from #1 to
#16.
Adjust application programming for each module when
more than 8 outputs are used. A second ROM module
must be added at a new address. Application linking for
outputs #9 to #16 of the original module must be
moved to the new module.
Power Source: 24VAC/20VA transformer No change.
Mounting: Plastic Track
14" w, 4" h, 1.5" d
DIN Rail
Multiple modules can be ganged together each with
dimensions per specification in this document.
Table 10. Product Comparison (COM).
Product Family: Novar Spectrum XIO Spectrum
Module: COM XIO-COM-S-H
Outputs: 10 compressor relay outputs
Outputs 1-5 are Form-A contacts
normally closed.
Outputs 6-10 are Form-C
contacts normally open and
normally closed.
8 compressor relay outputs
Form-C contacts normally open and normally closed.
Overrides: HOA switches for On-Off-Auto on
each output.
HOA switches for On-Off-Auto on each output.
Address Range: 16 to 19 (4 available)
Set address jumpers A1 & A0
16 to 19 (4 available)
Set Module Config switches 1 & 2
Application Programming: Application programming can
have links to outputs from #1 to
#10.
Adjust application programming for each module when
more than 8 outputs are used. A second COM module
must be added at a new address. Application linking
from outputs #9 to #10 of the original module must be
moved to the new module.
Power Source: 24VAC/20VA transformer No change.
Mounting: Plastic Track
14" w, 4" h, 1.5" d
DIN Rail
Multiple modules can be ganged together each with
dimensions per specification in this document.