XIO FAMILY OF SPECTRUM SYSTEM REMOTE INPUT/OUTPUT DEVICES
31-00360—01 10
Model and Part Numbers
MAINTENANCE
REPLACEMENT
The XIO family of modules with Spectrum communication
was designed with the intent to provide a solution for the
maintenance replacement of existing Novar Spectrum
refrigeration systems where diode type sensors are
approaching end of lifecycle. These products are not for
new application development. Legacy modules did not
support remote firmware upgrade and new modules will
not.
Refrigeration system engineering must review the
application design and wiring for each system prior to
module replacement. Legacy refrigeration control
systems impose constraints on the range of addresses
allocated for each type on the network.
The XIO communication status LED behavior has
changed to remain illuminated until successful
communication has been established. Consecutive
communications will flash the LED to on.
Wiring used for existing Spectrum systems will be
compatible with the XIO. Spectrum systems specified
communications cable as two conductor shielded cable.
(Belden #8761 equivalent, WIR-1010) XIO modules for
Spectrum match legacy polarity markings “(-) SH (+)” for
communication connections.
Table 8. Novar Part Numbers.
Part No. Product Description
XIO-RIM-S 8 Digital Inputs
SpectrumNET
XIO-RIMCT-S 8 Compressor Current Inputs
SpectrumNET
XIO-AOM-S 4 Analog Outputs
SpectrumNET
XIO-CIM-S 8 analog thermistor inputs in
NovarNet mode
7 analog thermistor inputs + 1
switch closure input in
Spectrum mode
XIO-8IM-S 8 voltage inputs in NovarNet
mode
8 current 4-20ma in Spectrum
mode
XIO-ROM-S 8 Relay Outputs
SpectrumNET
no HOA
XIO-CCM-S-H 8 Condenser Fan Relay Outputs
6 Condenser Fan Relay Outputs
and 2 dedicated Split Valve
Relay Outputs in Split Valve
mode
SpectrumNET
with HOA
XIO-COM-S-H 8 Compressor Relay Outputs
SpectrumNET
with HOA
ST-D24-XH Duct Sensor 10K Type II
Thermistor 9"
RCC-ST2K-2 Sensor, Temp, 2K NTC, w2.0M
Cbl
RCC-ST2K-5 Sensor, Temp, 2K NTC, w5.0M
Cbl
TR20VA001 Transformer, 20VA, 120:24, 1
hub + foot mount
(Only use for up to 2 modules)
709031000 Two-conductor shielded cable,
RS-485 (1000 foot reel)
730090000 24-VAC Transformer (40 VA)
770067000 24-VAC Transformer(100VA)
770007000 120:24VAC 100VA Transformer,
Hub or Foot mount, single
(Use for up to 5 modules)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Multisite XIO Series and is the answer not in the manual?

Honeywell Multisite XIO Series Specifications

General IconGeneral
BrandHoneywell
ModelMultisite XIO Series
CategoryI/O Systems
LanguageEnglish

Related product manuals