XIO FAMILY OF SPECTRUM SYSTEM REMOTE INPUT/OUTPUT DEVICES
31-00360—01 14
Replacement of Spectrum Case Input Module (8IMR/8IME)
Replacement of one legacy Novar Spectrum 8IM module requires installation of at least one XIO-8IM-S module.
Application
Programming:
Application programming can have links
to 8 low temp sensor inputs from #1 to #8
and 1 digital input.
Spectrum:
Same functionality for up to 7 low temp sensor inputs
and 1 digital input. Adjust application programming
when more than 7 input sensors are used. A second CIM
module may be added for the additional input.
Application linking for the 8th input point will be moved
to the new module.
Logic One:
Same functionality as legacy.
Power Source: 24VAC/2VA transformer or 24VDC/30mA
power source
Replace with 24VAC/20VA transformer.
Mounting: Plastic Track
17.25" L, 2.85" W, 1.1" D
DIN Rail
Multiple modules can be ganged together each with
dimensions per specification in this document.
Case Type Metal Enclosure, not waterproof. Location
of installation must be dry and not
refrigerated.
Plastic Enclosure, not waterproof. Location of
installation must be dry and not refrigerated.
Table 14. Product Comparison (8IMR/8IME).
Product Family: Novar Spectrum XIO Spectrum
Module: 8IMR/8IME XIO-8IM-S
Address Range: 00 to 63 (64 available)
Set address Dip Switches 1 to 6
00 to 63 (64 available)
Set Module Config switches 1 to 6
Special Modes: Individual hardware Jumpers for
Milliamp/Voltage on 8 inputs.
Baud rate select.
Mode select for Spectrum 8IM or Logic
One.
8 current 4-20ma in Spectrum mode.
No changes to baud rate or mode select.
Inputs: 8 universal inputs
1 digital input as dual temp select
Spectrum:
8 low temp inputs, diode sensors must be replaced with
low temp 2k thermistor sensors. For NovarNet mode
only.
No digital input is supported.
Logic One:
8 voltage input sensors, 1-5VDC. Use a shunt resistor to
convert from voltage to current input. Shunt resistor of
250-Ohms gets installed across the input terminals.
Special Modes: Baud rate select.
Spectrum 8IM or Logic One mode select.
No change.
Application
Programming:
Application programming can have links
to eight low temp sensor inputs from #1 to
#8 and one digital input.
Spectrum:
No digital input for dual temp selection is supported.
Default reading returned from the module is a logic low
state.
Logic One:
Same functionality as legacy.
Power Source: 24VAC/6.5VA transformer 24VAC/20VA transformer
Mounting: Plastic Track
17.25" L, 2.85" W, 1.1" D
DIN Rail
Multiple modules can be ganged together each with
dimensions per specification in this document.
Table 13. Product Comparison (CIM2). (Continued)
Product Family: Novar Spectrum XIO Spectrum