XIO FAMILY OF SPECTRUM SYSTEM REMOTE INPUT/OUTPUT DEVICES
13 31-00360—01
Replacement of Spectrum Analog Output Module (AOM)
Replacement of one legacy Novar Spectrum AOM module requires installation of one XIO-AOM-S module.
Replacement of Spectrum Case Input Module (CIM2)
Replacement of one legacy Novar Spectrum CIM2 module requires installation of at least one XIO-CIM-S module.
Table 12. Product Comparison (AOM).
Product Family: Novar Spectrum XIO Spectrum
Module: AOM XIO-AOM-S
Address Range: 56 to 63 (8 available)
Set address jumpers A2, A1 & A0
56 to 63 (8 available)
Set Module Config switches 1, 2 & 3
Outputs: 4 Analog outputs, 0 to 10VDC 4 Analog outputs, 0 to 10VDC on outputs #1-#4. No
function intended for outputs #5-#10.
Application
Programming:
Each programmed module can have links
to outputs from #1 to #4 for analog
outputs.
No change
Power Source: 24VAC/6.5VA transformer Replace with 24VAC/20VA transformer.
Mounting: Plastic Track
14" w, 4" h, 1.5" d
DIN Rail
Multiple modules can be ganged together each with
dimensions per specification in this document.
Table 13. Product Comparison (CIM2).
Product Family: Novar Spectrum XIO Spectrum
Module: CIM2 XIO-CIM-S
Address Range: 00 to 63 (64 available)
Set address Dip Switches 1 to 6
00 to 63 (64 available)
Set Module Config switches 1, 2 & 3
Special Modes: Individual hardware Jumpers for
Milliamp/Voltage on 8 inputs.
Baud rate select.
Mode select for Spectrum 8IM or Logic
One.
Jumpers to select input type are not supported. A shunt
resistor of 250-Ohms may be added externally for
current inputs instead of jumpers.
No changes to baud rate or mode select.
Inputs: 8 inputs for refrigeration case temperature
sensors. Low temp glass diode sensors.
1 digital switch closure from a dual
temperature case.
Spectrum:
7 low temp inputs, diode sensors must be replaced with
low temp 2k thermistor sensors.
1 digital input
Logic One:
No change for 8 voltage input sensors, 1-5VDC. Use a
shunt resistor to convert from voltage to current input.
Shunt resistor of 250-ohm gets installed across the
input terminals.
User Interface: LED Display to show case temperature
and status of each input local to
installation site. PB1 Calibration Push
Button. Step Display Push Button.
No support for user interface or calibration.