SPYDER MODEL 5 ROOM CONTROLLERS − INSTALLATION GUIDE
31-00281ES-01 (EN1B-0664GE51 R0819) 2
DIMENSIONS AND MOUNTING
Housings
The controller is available in two housing sizes, both
conforming to IP20:
▪ WEB-RL6N (large housing): W x L x H =
4-5/16 x 7-13/16 x 2-5/16 in (110 x 198 x 59 mm) and
▪ WEB-RS5N (small housing): W x L x H =
4-5/16 x 6-3/8 x 2-5/16 in (110 x 162 x 59 mm)
See also Fig. 2 and Fig. 3.
Fig. 3. WEB-RS5N dimensions in inch (mm)
The unit is suitable for mounting on a standard rail, on
walls, as well as in wiring cabinets or fuse boxes.
NOTE:
- IP20 provides, Ingress Protection against solid objects
over 12.5mm e.g. hands, large tools. No protection
against liquids.
- IP30 provides, Ingress Protection against solid objects
over 2.5mm e.g. wire, small tools. No protection against
liquids
Terminal Protection Covers for IP30
In the case of controllers mounted outside of a cabinet,
before applying power to the device, Terminal Protection
Covers (10-pc. bulk packs, order no.: IRM-RLC for large
housings and IRM-RSC for small housings) must be
mounted so as to provide IP30.
Fig. 4. Large housing, with terminal protection covers,
dimensions in inch (mm)
Fig. 5. Small housing, with terminal protection covers,
dimensions in inch (mm)
DIN Rail Mounting/Dismounting
Fig. 6. Mounting and dismounting
The unit can be mounted onto the DIN rail simply by
snapping it into place. It is dismounted by gently pulling the
stirrup(s) located at the base of the housing (see Fig. 6).