22
Specifications
Model Nr.: TH6320ZW2003
Model Name: T6 Pro ZWave Thermostat
Model Description: Programmable ZWave
thermostat with touchscreen
Stages:
Up to 3 Heat / 2 Cool Heat Pump
Up to 2 Heat / 2 Cool Conventional
Power requirements:
Battery power: AA alkaline battery 3pcs.
C-wire input: 1830VAC; 50Hz60Hz
Electrical Ratings:
Terminal Voltage
(50/60Hz)
Running
Current
W Heating 1830 Vac 0.021.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux) Heating 1830 Vac 0.021.0 A
E Emergency Heat 1830 Vac 0.020.5 A
Y Compressor
Stage 1
1830 Vac 0.021.0 A
Y2 Compressor
Stage 2
1830 Vac 0.021.0 A
G Fan 1830 Vac 0.020.5 A
O/B Changeover 1830 Vac 0.020.5 A
L/A Input 1830 Vac 0.020.5 A
Dimension: 4.09” x 4.09” x 1.06”
Display size: 6.55 sq. in.
Temperature ranges:
Adjustable Heat Temperature Range Setting:
4090 °F (4.532.0 °C)
Adjustable Cool Temperature Range Setting:
5099 °F (10.037.0 °C)
Operating ambient temperature range:
37102°F (2.7838.89 °C)
Temperature Sensor Accuracy:
± 1.5 °F at 70 °F (0.85 °C at 21.0 °C)
Physical Dimensions in inches (mm) (H x W x D):
T6 PRO ZWave Thermostat (TH6320ZW2003):
45/64 x 45/64 x 11/16 (104 x 104 x 27)
UWP Mounting System (included):
29/32 x 213/64 x 243/64 (58 x 56 x 10)
Standard Installation Adapter (included):
329/32 x 357/64 x 21/32 (99 x 99 x 17)
Decorative Cover Plate – Small (included):
449/64 x 449/64 x 11/32 (121 x 121 x 9)
Decorative Cover Plate – Large (THP2400A1068):
67/64 x 67/64 x 9/32 (155 x 155 x 7)
ZWave Radio:
Frequency (USA and Canada): 908.42 MHz
Certified: ZWave Plus
Generic Device Type: Thermostat
Node type (C-wire): Always On Slave (AOS)
Node type (Battery): Listening Sleeping Slave (LSS)
ZWave Chipset: ZM5202AU
Supported ZWave Command Classes:
ZWave Plus Info V2
Supervision V1
Transport Service V2
Association V2
Version V2
Association Group Information V2
Basic V1
Battery V1
Clock V1
Configuration V4
Device Reset Local V1
Manufacturer Specific V2
Sensor Multilevel V5
Notification V3
Powerlevel V1
Security 2 V1
Thermostat Fan Mode V3
Thermostat Fan State V1
Thermostat Mode V3
Thermostat Operating State V1
Thermostat Setpoint V2
NOTES:
Thermostat Mode V3:
• Some of the reported modes are manufacturer
specific if not covered by the ZWave command
class.
Basic V1 (basic set command implementation):
• Value 0x00 Device goes to Energy saving setting
(AWAY mode)
• Values 0x010x63 and 0xFF Device goes to
Comfort setting (HOME mode)
Notification V3:
• Notification V3 is enabled by default (Power
management alarm handling). Notification
Type: Power Management (0x08). Notification
Events: AC mains disconnected (0x02), AC mains
re-connected (0x03).
Security:
• All supported ZWave Command classes are
supported securely (S2 unauthenticated), except
Transport Service V2, Security 2 V1 and ZWave
Plus Info V2
Association V2:
• Group ID: 1; Maximum Nodes: 1; Description:
ZWave Plus Lifeline
• Command Classes reported: Multilevel Sensor,
Thermostat Setpoint, Thermostat Mode
• Thermostat Fan Mode, Thermostat Operating
State, Thermostat Fan State, Basic