Troubleshooting 42
Off
Flashin
g red
Off Off
Flashin
g red
Off
On1 beep
every 5
seconds
Yes
On batteryInput
voltage is out of range
(on page 43)
Flashing
red
Flashin
g red
Flashin
g red
Flashin
g red
Flashin
g red
Flashing
red
On
Continuous
No
Internal UPS fault
condition (on page
44)
Red Off Off Off Off Off
On
Continuous
Yes
Self-test failure
("Battery condition"
on page 43)
Flashing
red
Off Off Off
Flashin
g
green
Off
On
Continuous
Yes
REPO condition (on
page 44)
Off Off Off Red Off Off
On1 beep
every 5
seconds
Yes
Site wiring condition
(on page 44)
Flashing
red
Off Off Off Off Red
On
Continuous
Yes
UPS power capacity is
exceeded ("Overload
condition" on page
44)
For the location of individual LEDs, see "UPS front panel LED indicators (on page 8)."
UPS is in Auto-Bypass mode
Action:
1. If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HP Power Manager user
guide available for download from the HP website (http://www.hp.com/go/rackandpower
).
2. Verify that no blockage of airflow to the front bezel and rear panel exists.
3. If the LED does not turn off, replace the electronics module. ("Replacing the UPS electronics module"
on page 33)
General alarm condition
Action:
1. If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general alarm condition, see the HP Power Manager
user guide available for download from the HP website (http://www.hp.com/go/rackandpower
).
2. Check the batteries:
a. Allow the UPS batteries to charge for 24 hours.
b. If the Battery Fault LED is red, replace the batteries ("UPS battery replacement procedure" on
page 36).
3. Reduce the load:
a. Power down the UPS ("Powering down the UPS" on page 31).

Table of Contents

Other manuals for HP J4367A - UPS R3000 XR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP J4367A - UPS R3000 XR and is the answer not in the manual?

HP J4367A - UPS R3000 XR Specifications

General IconGeneral
BrandHP
ModelJ4367A - UPS R3000 XR
CategoryUPS
LanguageEnglish

Related product manuals