EasyManuals Logo
Home>HP>UPS>R/T3000 G2

HP R/T3000 G2 User Manual

HP R/T3000 G2
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Maintenance 46
1.
Read and observe the requirements in "Important battery safety information (on page 46)" and "Battery
care and storage guidelines (on page 46)."
2. Follow the instructions in "UPS battery replacement procedure (on page 47)."
Important battery safety information
WARNING: The unit contains sealed lead-acid battery modules. To prevent fire or chemical
burns:
Do not attempt to recharge batteries after removal from the unit.
Do not disassemble, crush, or puncture the batteries.
Do not short the external contacts of the batteries.
Do not immerse the batteries in water.
Do not expose to temperatures higher than 60°C (140°F).
WARNING: To prevent personal injury from hazardous energy:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Do not place tools or metal parts on top of batteries.
WARNING: To prevent personal injury, prepare the area and observe all materials-handling
procedures when transporting a battery module. Battery modules weigh 20 kg (44.1 lb).
NOTE: Replace all battery modules at the same time.
Battery care and storage guidelines
Minimize the amount of time the UPS uses battery power by matching the UPS configuration with the
utility voltage. Refer to "Configuring the UPS (on page 42)."
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of
the UPS regularly with a vacuum cleaner.
Maintain the ambient temperature at 25°C (77°F).
If storing a UPS for an extended period, recharge the batteries every 6 months:
CAUTION: Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep these
batteries charged while in storage is implemented.
a. Connect the UPS to utility power.
b. Allow the UPS to remain in Standby mode.
c. Allow the UPS to charge the batteries for at least 24 hours.
d. Update the battery recharge date label.
Determining when to replace batteries
When the Battery Fault LED illuminates, batteries might need to be replaced within 30 to 60 days.

Table of Contents

Other manuals for HP R/T3000 G2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R/T3000 G2 and is the answer not in the manual?

HP R/T3000 G2 Specifications

General IconGeneral
BrandHP
ModelR/T3000 G2
CategoryUPS
LanguageEnglish

Related product manuals