Installation and configuration 25
Connecting the UPS cord retention clips
Charging the UPS batteries
With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
80 percent of their capacity within 3 hours
100 percent of their capacity within 48 hours
Starting power to the load
Start power to the load by placing the UPS in Operate mode.
IMPORTANT: AC power must be available the first time the UPS is started.
Configuring the UPS Network Module
NOTE: For more information about the UPS Network Module, see the HP Infrastructure
Management Pack software CD and documentation for complete details.
Before configuring the UPS Network Module, be sure that the network cable is connected.
Connecting the configuration cable
1. Connect the DB-9 connector on the DB-9 to RJ-45 cable to a serial connector on the host computer.

Table of Contents

Other manuals for HP R5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R5000 and is the answer not in the manual?

HP R5000 Specifications

General IconGeneral
Output Voltage230V
Form FactorRack-mountable
Rack Height3U
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage230V
Frequency50/60 Hz
Battery Recharge Time3 hours
Transfer Time0 ms
Operating Temperature0 - 40 °C
Battery TypeSealed Lead Acid (SLA)
InterfaceUSB, Serial
Output Power Capacity4500 Watts
Efficiency95%
Power Capacity5000 VA
Dimensions43.2 x 66 x 13 cm