EasyManuals Logo
Home>HP>UPS>R5000

HP R5000 User Manual

HP R5000
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Specifications 52
Feature Specification
Surge suppression
High-energy 6500 A peak
Noise filtering
MOVs and line filter for normal and common mode
use
Battery specifications
Feature Specification
Type
Each model contains maintenance-free, sealed, valve
regulated lead-acid batteries with an 8-year minimum float
service life at 25°C (77°F).
Voltage
The battery modules have a battery string voltage of 216 V.
Charging
Complete charge takes no more than 48 hours.
Approximately 3 hours to 80 percent capacity at default
nominal utility voltage and no load.
Average battery runtime
Average battery runtimes are approximate and vary depending on connected equipment, configuration,
battery age, temperature, and so on. These estimates are based on the batteries at beginning of life.
Load % Estimated
battery runtime
(minutes)
Runtime with
one ERM
(minutes)
Runtime with
four ERMs
(minutes)*
20
44 123 436
50
16
44
145
80
7 25 83
100
5.7 20 64
* NA/JPN model only
Minimum battery runtime
Minimum battery runtimes are at beginning of life.
Load % Internal battery
runtime
(minutes)
Runtime with
one ERM
(minutes)
Runtime with
four ERMs
(minutes)*
20
36
100
360
50
12 36 115
80
6 23 80
100
5 18 58
* NA/JPN model only

Table of Contents