6.0 Installation
Refer to the Specifications section for dimensional drawings and connection specifications. Use these
drawings to find a suitable location for the appliance.
6.1 Code requirements
The appliances are tested and certified under CSA STD.C22.2 No.60335-1 and 60335-2-40. Below
are the code requirements for every installation.
Canada and USA
Conform to local codes, or in the absence of these, with the latest editions of UL STD.60335-1 and
60335-2-40 / CSA STD. C22.2 No. 60335-1 and 60335-2-40.
Table 4 Code requirements by country
Warning
This appliance shall be installed in accordance with national wiring regulations.
6.2 Determining location of the appliance
The hydronic heat pumps are designed and approved for outdoor installation. .
A = 1 ft 8" / 0.5 m minimum
B = 4 ft 11" / 1.5 m minimum
C = 3 ft 3½" / 1.0 m minimum
D = 1 ft 8" / 0.5 m minimum
Table 5 Clearance distances for hydronic heat pump mounting sites