The SF series units include a factory installed and pre-wired pump. The pump
may not be able to supply adequate ow for the heat emitter circuits. A system
heating pump switched through a separate relay or control box may be needed.
SEQUENCE OF OPERATION
The boiler operates in a similar way for both a space heating and a domestic hot
water call for heat. When the boiler is powered up the controller enters a self-
diagnostic mode, and displays “2” in the Service Display.
The Sequence of Operation is as follows:
1. The boiler receives a call for heat from closing terminals X13.1 and X13.2
(24 volts section). The boiler can also receive a call from Domestic Hot Water
heating from the internal ow sensor, or from a 10KΩ sensor or aquastat
(X13.4 and X13.5 in 24V terminal).
2. The boiler does a safety check and energizes the fan for a pre-purge
(Service Display = 3).
3. Once the 5-second pre-purge is compete, the boiler enters a 5-second trial
for ignition (Service Display = 4). If the boiler fails to ignite, the boiler will
complete a 5-second inter-purge then another 5-second trial for ignition. This
is repeated 4 times before a hard lock-out occurs. The Return button must be
pressed to reset the controller and to allow for another attempt.
4. Once the burner is lit and ame has been proven the boiler operates as it is
programmed (Service Display = for Space Heating or for Domestic
Hot Water).
5. If the boiler reaches its target temperature and there is still a call for heat
or hot water the Burner will turn off (integral pump runs unless call is on-
demand dhw ). (Service Display = 1)
6. After the call for heat is satised, the boiler pump will operate for an
adjustable amount of time (Service Display = 0).
7. If the burner is on to maintain the heat exchanger temperature for DHW
Comfort mode or for Freeze Protection mode (Service Display = 7).
8. If the burner is on to maintain the heat exchanger temperature for DHW
Comfort mode or for Freeze Protection mode (Service Display = 7).