Table 34. Dimensions for doors (continued)
Door model Width Height Depth Weight
Standard side
covers
10 mm (0.4 in.)
each
1740 mm (68.5 in.)
each
1042 mm (41.0 in.)
each
18 lbs 8.25 kg (18
lb) each
FC 6101 front door
(OEM)
639 mm (25.2 in.) 1740 mm (68.5 in.) 56 mm (2.3 in.) 14 kg (31 lb)
FC 6068 front door,
high perforation
639 mm (25.2 in.) 1740 mm (68.5 in.) 56 mm (2.3 in.) 14 kg (31 lb)
FC 6248 acoustic
doors, front and
rear
639 mm (25.2 in.)
each
1740 mm (76.6 in.)
each
198 mm (7.8 in.)
each
12.3 kg (27 lb)
each
Table 35. Electrical
1
Electrical characteristics Properties
Power source loading maximum in kVA
2
8.4 (FC 6117
3
)
8.4 (FC EPB8
3,4
)
Notes:
1. The total rack power can be derived from the sum of the power that is used by the drawers in the
rack.
2. For FC EPB8, each side can support a maximum of 600 amps (A) and 10 circuit breakers. The PDP
can hold up to twenty (ten per power source) circuit breakers with ratings between 5 A and 90 A.
Each power source supports up to 8.4 kVA.
3. For more information about FC 6117 and FC EPB8, see “Model 7014-T00 rack with optional DC
power distribution panel” on page 25.
4. Preliminary data is subject to change.
See your individual server or hardware specications for temperature and humidity requirements.
Rack noise levels depend on the number and type of drawers installed. See your server or hardware
specications for specic requirements.
Note: All rack installations require careful site and facilities planning that are designed to both address
the cumulative drawer heat output and provide the airflow volume rates necessary to comply with drawer
temperature requirements. All rack installations require careful site and facilities planning that are
designed to address both the cumulative drawer heat output and provide the airflow volume rates
necessary to comply with drawer temperature requirements. Rack airflow requirements depend on the
number and type of drawers installed.
Note: Acoustic doors are available for IBM racks. Feature code 6248 is available for the 0551 and 7014-
T00 racks. Feature code 6249 is available for 7014-T42 racks. The overall sound reduction is
approximately 6 dB. The doors add approximately 381 mm (15 in.) to the depth of the racks.
Related reference
7014-T00 and 7014-T42 rack weight distribution and floor loading
24
Power Systems: Site and hardware planning

Other manuals for IBM 9009-22A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 9009-22A and is the answer not in the manual?

IBM 9009-22A Specifications

General IconGeneral
BrandIBM
Model9009-22A
CategoryPower Supply
LanguageEnglish

Related product manuals