4 . T R O U B L E S H O O T IN G
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptoms
Possible causes
Remedy
No indication and alarm even though the
main is normal.
The AC input power is not
correctly connected.
Check if input power cord
firmly connected to the
mains.
The AC input is connected
to the UPS output.
Plug AC input power cord
to AC input correctly.
The icon and the warning code
flashing on LCD display and alarm is
sounding every 2 seconds.
EPO function is activated.
Set the circuit in close
position to disable EPO
function.
The icon and flashing on LCD
display and alarm is sounding every
2 seconds.
Line and neutral
conductors of UPS input
are reversed.
Rotate mains power
socket by 180° and then
connect to UPS system.
The icon and flashing on
LCD display and alarm is sounding every
2 seconds.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
Fault code is shown as 27 and the icon
is lighting on LCD display and alarm is
continuously sounding.
Battery voltage is too high
or problem with the
charger.
Contact your dealer.
Fault code is shown as 28 and the icon
is lighting on LCD display and alarm is
continuously sounding.
Battery voltage is too low
or problem with the
charger.
Contact your dealer.
The icon and the icon
are flashing on LCD display and alarm is
sounding every second.
UPS is overloaded.
Remove excess loads
from UPS output.
Fault code is shown as 43 and The icon
is lighting on LCD display
and alarm is continuously sounding.
The UPS shut down
automatically because of
an overload at the UPS
output.
Remove excess loads
from UPS output and
restart it.
Fault code is shown as 14 and alarm is
continuously sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 1, 2, 3, 11 and 41 on
LCD display and alarm is continuously
sounding.
A UPS internal fault has
occurred.
Contact your dealer

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series and is the answer not in the manual?

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelE3 PERFORMANCE RT Series
CategoryUPS
LanguageEnglish

Related product manuals