INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 06 17 AA 59 205 05
7 . S p e c i f i c a t i o n s
[81-145 VAC] or [162-290 VAC]**
Voltage Regulation
(normal Mode)
[110/115/120/127 VAC] or [208/220/230/240 VAC]**
Voltage Regulation
(Batt. Mode)
±1.5%(before battery alarm)
Frequency Range
(Batt. Mode)
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
95% for LV versions (110V) ; 97% for HV versions (230V)**
93% for LV versions (110V); 95% for HV versions (230V)**
88% for LV versions (110V)
89% for 208 HV versions
(230V)**
90% for LV versions (110V)
91% for HV versions (230V)**
90% for LV versions (110V)
92% for HV versions (230V)**
4 hours recover to 90% capacity
Overload, short, discharge, and overcharge protection
Battery Mode, Low Battery, Overload, Battery Replacement, Fault
0-90 % RH @ 0- 40°C (non-condensing)
Less than 45dB at 1 meter
Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC
Power management from SNMP (VMWare
©
compatible) manager and web browser
EN62040-2: 2006+AC: 2006 (EN 61000-3-2: 2014, EN61000-4-2:2009, EN61000-4-3:2006+A2: 2010,
EN61000-4-4: 2012, EN61000-4-5: 2006, EN61000-4-6: 2014, EN61000-4-8: 2010, EN61000 -2-2: 2002)
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC.
**Low voltage (110V) and High voltage (230V) are different products.
***Product specifications are subject to change without further notice.