ORIG,SE,SG:
CONTROLLER LOCK-UP. UNIT WILL NOT STOP
OR READY TO START WILL NOT START
= UNIT RUNNING. PUSHING THE STOP BUTTON DOES NOT CAUSE ANYTHING TO
HAPPEN AND NO ALARMS ARE INDICATED, OR READY TO START IN THE DISPLAY
AND PRESSING THE START BUTTON DOES NOT CAUSE START OR ALARM. CYCLING
POWER WILL RESET BUT PROBLEM OCCURS AGAIN.
SE CONTROLLER
SG CONTROLLER
ORIGINAL INTELLISYS
16 VAC C.T. FEED
CIRCUIT INTERMITTENT
CHECK WIRING FROM T1 TO
J4-29, 30, 31.
SEE PARAGRAPH 1.4
24 VAC FEED CIRCUIT
INTERMITTENT
CHECK WIRING FROM T1
TO J1 - 1 & 2.
SEE PARAGRAPH 3.3
BAD MEMBRANE
USE SE I/O
MEMBRANE TEST
KIT TO VERIFY
BAD MEMBRANE
TEST MEMBRANE
SEE PARAGRAPH
5.0
EXCESSIVE TEMPERATURE
REDUCE CONTROLLER AMBIENT
TO <160°F
SEE PARAGRAPH 1.7
EXCESSIVE MOISTURE. WATER
LEAKING INTO CONTROLLER. SEE
PARAGRAPH 1.6
COMM PORT
SE USE I/O TEST KIT
SEE SHEET FOR BLANK DISPLAY
FOR OTHER OPTIONS, PAGE 7 & 8
115 VAC FEED CIRCUIT
INTERMITTENT
CHECK WIRING AND
VOLTAGE FROM BTS1 -
33 & 3.
YES. CHECK VOLTAGE AT TRANSFORMER T3
AND CONNECTION J1
J1 1 & 6 SHOULD BE 110-130 VAC
J1 2 & 5 SHOULD BE 12-14 VAC
J1 2 & 4 SHOULD BE 6-7 VAC
J1 3 & 5 SHOULD BE 6-7 VAC
IF NOT, BAD T3 TRANSFORMER
IS IT 110-130 VAC?
NO. PROBLEM WITH T1
TRANSFORMER OR
BAD MEMBRANE
SEE PARAGRAPH
5.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ingersoll-Rand INTELLISYS SSR Series and is the answer not in the manual?

Ingersoll-Rand INTELLISYS SSR Series Specifications

General IconGeneral
BrandIngersoll-Rand
ModelINTELLISYS SSR Series
CategoryAir Compressor
LanguageEnglish

Related product manuals