Goodrive20 inverters Function Parameters
33
Function
code
Name Detailed instruction of parameters
Default
value
Modify
When the frequency used exceeds the default carrier
frequency, the inverter needs to derate 10% for each
additional 1k carrier frequency.
Setting range:1.0~15.0kHz
P00.15
Motor
parameter
autotuning
0: No operation
1: Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when high
control accuracy is needed.
2: Static autotuning 1(autotune totally); It is suitable in the
cases when the motor can not de-couple form the load. The
antotuning for the motor parameter will impact the control
accuracy.
3: Static autotuning 2(autotune part parameters); when the
current motor is motor 1, autotune P02.06, P02.07, P02.08
AVR function
selection
0:Invalid
1:Valid during the whole procedure
The auto-adjusting function of the inverter can cancel the
impact on the output voltage of the inverter because of the
bus voltage fluctuation.
1 ○
Function
restore
parameter
0:No operation
1:Restore the default value
2:Clear fault records
3: Lock all function codes
Note: The function code will restore to 0 after finishing the
operation of the selected function code.
Restoring to the default value will cancel the user password,
please use this function with caution.
0 ◎
P01 Group Start-up and stop control
P01.00
Start mode
0:Start-up directly:start from the starting frequency P01.01
1:Start-up after DC braking: start the motor from the starting
frequency after DC braking (set the parameter P01.03 and
P01.04). It is suitable in the cases where reverse rotation
may occur to the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2
The direction and speed will be tracked automatically for the
smoothing starting of rotating motors. It suits the application
with reverse rotation when big load starting.
0 ◎