Settings
6 720 643 409 (2010/03)
73
> Inputs
The status of all inputs is displayed here. Pressostats
and motor cut-outs are shown for each heat pump. In
addition, any alarms for shunted additional heat, status
for external inputs and protective anode are shown.
Only connected inputs are displayed.
> Outputs
All components can be manually operated individually
here to check function.
>> Manual operation time
B Set the number of minutes for manual operation.
Different vital components can be put into operation/
turned off separately.
With 0min, status, e.g., On or Off, is displayed for
each component.
Manual operation is possible for the following
components (only the ones that are installed are
displayed):
>> G1 Heating circuit pump
>> Heat pump x
>>> Q21 Three-way valve(Heating/Hot water)
>>> G2 Heat carrier pump
>>> G3 Collector circuit pump
>>> Compressor
>> Hot water electric heater
>> Hot water circulation pump
>> Circuit 2, 3...
>>> Circulation pump
>>> Mixing valve signal
>>> Mixing valve open
>>> Mixing valve close
>> Connect heater 1 to heat pump
>>> Electric additional heat triac(all Off/On)
>>> Electric additional heat relay(all Off/On)
>> Alarm buzzer(all Off/On)
>> General alarm
> Circulation pumps
>> Operation alternative heating circuit pump G1
B Select if circulation pump G1 should run continuously
or in optimised operation. The setting applies to G1 of
all circuits.
Continuous means that G1 is always in operation
during the heating season.
Automatic means that the circulation pump runs in
approx. 10 min, stands idle for 10 min, and so on, if it
is in winter operation and there has not been any
heating demand for 40 min. Automatic operation is
cancelled when heating demand arises or winter
operation is disabled.
G1 stands idle (apart from anti-seizure operation) if it
is summer operation.
T2 Outdoor, display T2 correction
Temperatures heat
pump x
T1 Start/stop limits
compressor
T6,T8,T9,T10,T11 display,
correction
T3 hot water start
T8 hot water stop
Circuit x T1 set point
T1 display, correction
T5, display, correction,
damping
Room temperature set point
value
Menu dial influence, display
(CANbus)
Hot water T3 display, correction
Extra hot water stop
temperature
Hot water peak stop
temperature
Tab. 134Temperature display
F value 0min
Lowest value 0min
Highest value 240min
Tab. 135Manual operation time
Use the manual operation function on
commissioning in order to check if the
installed components work.
Factory setting Continuous
Alternative Continuous/Automatic
Tab. 136G1