18.4 Operating temperatures
Check the temperatures in the heat carrier and collector
circuit after 10 minutes of operation:
Temperature difference between heating forward
flow and return approx. 7 ... 10 K.
Temperature difference between collector circuit in
and out approx. 2 ... 5 K, recommendation: 2 ... 3 K.
When the temperature difference is too small:
B Reduce the speed of the corresponding circulation
pump (G2 or G3) in order to obtain a lower flow.
When the temperature difference is too great:
B Increase the speed of the corresponding circulation
pump (G2) in order to obtain a greater flow.
Fig. 62
P2 Heat carrier pump G2
P3 Collector circuit pump G3
t
SA
Temperature collector circuit out T11
t
SE
Temperature collector circuit in T10
t
HV
Temperature heat transfer fluid out T8
t
HR
Temperature heat transfer fluid in T9
0 K
10 K
7 K
6 K
9 K
P2
P2
P2
t
HV
- t
HR
3 K
5 K
2 K
P3
P3
P3
P3 ( )
P2 ( )
P2 ( )
t
SE
- t
SA
6 720 612 299-04.3O

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IVT E11 and is the answer not in the manual?

IVT E11 Specifications

General IconGeneral
BrandIVT
ModelE11
CategoryHeat Pump
LanguageEnglish

Related product manuals