Technical information
6 720 643 409 (2010/03)
21
7.3 Technical information
7.3.1 C6 - C11
Unit C6 C7 C9 C11
Mode fluid/water
Heating output (B0/W35)
1)
kW 5,5 7,2 8,8 10,3
Heating output (B0/W45)
1)
kW 5,1 6,6 8,2 9,9
COP (B0/W35)
1)
1) According to EN 14511
–
4,1 4,2 4,2 4,4
COP (B0/W45)
1)
– 3,2 3,3 3,3 3,5
Heat transfer fluid
Nominal flow l/s 0,30 0,38 0,46 0,57
Permit external pressure drop kPa 49 45 44 80
Max. pressure bar 4
Contents (internal) l 6
Operating temperature °C –5... +20
Connection mm Ø28
Compressor
Type – Mitsubishi Scroll
Weight refrigerant R407c kg 1,6 1,6 1,8 2,4
Max. pressure bar 31
Heating system
Nominal flow l/s 0,20 0,25 0,31 0,38
Min./max. flow temperature °C 20/65
Max. permitted operating pressure bar 1,5
Heating water incl. outer shell hot water heater l 47
Connection mm Ø22
Hot water
Max. output with/without 6kW electric additional heat kW 5,5/11,5 7,0/13,0 8,4/14,4 10,2/16,2
Volume hot water l 185
Min./max. permitted operating pressure bar 2/10
Connection mm Ø22
Values for electrical connection
Electrical supply 400V 3N~50Hz
Fuse, slow; with electric add. heat 3 kW/6 kW A 16 16 16/20 16/20
Nominal power consumption compressor (B0/W35) kW 1,33 1,64 1,99 2,22
Max. current with soft starter
2)
(accessories)
2) No soft starter in C6
A < 30
Enclosure class IP X1
General
Permitted ambient temperature °C +10... +35
Sound pressure level
3)
3) According to EN ISO 11203
dBA
31 34 36 35
Dimensions (height x depth x width) mm 600 x 645 x 1800
Weight (copper/stainless steel hot water heater) kg 230/200 231/201 240/210
218
(stainless
steel)
Tab. 10 Technical data