TEC1100 Series Thermostat Technical Bulletin 17
Point Name
(Cont.)
TEC
Point
Type/
Addr.
N30
(CPN/
FAC)
Object
Type
BAS
Model
Point
Type
Override Range TEC
1101
TEC
1102
TEC
1103
Y1 State
BD-6 N2 BI
(BI)
CSBD BD6 0 = Off, 1 = On Cool 1 Comp 1 Cool 1
Y2 State
BD-7 N2 BI
(BI)
CSBD BD7 0 = Off, 1 = On Comp 2 Cool 2
G State – Fan
BD-8 N2 BI
(BI)
CSBD BD8 0 = Off, 1 = On
♦♦
Temp Units
ac
BD-9 N2 BO
(BO)
CSBD BD9 0 = °C, 1 = °F
♦♦
Wrench BI
b
BI-1
N2 BI
(BI)
CSBI BI1 0 = Normal, 1 = Alarm
♦♦
Temp Alarm
b
BI-2 N2 BI
(BI)
CSBI BI2 0 = Normal, 1 = Alarm
♦♦
Filter
b
BI-3 N2 BI
(BI)
CSBI BI3 0 = Normal, 1 = Alarm
♦♦
Notes:
a Commandable
b Can be a COS alarm to the BAS or NDM to initiate a dial-out.
c On the Metasys NCM system, map BD9 Temp Units Mode as a Binary Output (BO) object in a Control System
(CS) object with Autorestore and Local Control set.
The Controller Point Type is the fixed point definition inside the controller. The CPN/FAC point is the software point
definition inside the Companion software. The BAS Model Point type is the definition inside the model file. An NCM
CS object must be used to retrieve the data.
Control of the Analog Data (AD) objects is the last command received is the one that controls the thermostat. For
example, if the Metasys system sends a Night override, but the occupant selects Day mode, the TEC goes into Day
mode.
To install the thermostat cover lock:
1.
Place the ends of the lock piece (included with unit) under the lock
pins extending from the bottom of the mounted base. The tab in the
middle of the lock piece extends downward from the mounted base
(Figure 13).
2.
Press the lock piece up and into the base while gently prying open the
thermostat to release the lock. Use caution to avoid cracking the
thermostat base or cover.
Installing the
Thermostat
Cover Lock

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls METASYS TEC1103 and is the answer not in the manual?

Johnson Controls METASYS TEC1103 Specifications

General IconGeneral
BrandJohnson Controls
ModelMETASYS TEC1103
CategoryThermostat
LanguageEnglish

Related product manuals