TEC1100 Series Thermostat Technical Bulletin 7
Select Dual Inline Package (DIP) switches to perform a variety of
different functions: fan runtime delay, keyboard disable, and multistage
heating or cooling.
Note: Before selecting a minimum On/Off time for the TEC1100 Series,
verify the equipment can tolerate the following hourly maximum
cycle rates: 7.5 cycles per hour when using 4-minute On/Off
(preferred for energy savings) or 15 cycles per hour when using
2-minute On/Off.
TEC1101 Single-Stage Wiring Configuration and DIP Switch Settings
Refer to Figure 3, Figure 5, and Figure 7 for DIP switch settings.
Table 5: TEC1101 Single-Stage DIP Switch Selections
DIP Switch Selection Description
1
On Allows 2-minute minimum On/Off time for heating or cooling equipment.
Off Allows 4-minute (preferred) minimum On/Off time for heating or cooling equipment.
2
On*
Locks the keyboard, disabling buttons to prevent tampering. The Day/Night mode
button can select 1-hour override.
Off Unlocks the keyboard.
3
On In Heating mode, with a call for heat, the plenum temperature switch controls fan
operation. However, Cooling mode allows the fan to operate immediately with a
call for cooling. The temperature switch is wired directly to the fan.
Off Heating or Cooling mode allows the fan to operate immediately with a call for heat
or cooling.
* When DIP Switch 2 is on, you can only use the Day/Night mode button to select 1-hour override to occupied
setpoints if in Night mode. All other buttons are read-only. You can also view the N2 address.
Hcn2diwi
RS1
TEC1101
Heating
Cooling
Fan
Common
Keyboard LockedKeyboard Unlocked
O
N
1
3
2
with Call for Heat
Heat/Cool: 4 Minute
(Minimum On/Off)
Heat/Cool: 2 Minute
(Minimum On/Off)
Fan On with Plenum
Temperature Switch
RS+V
Power in
CLK1
CLK2
RS2
Fan Immediate
N2+
N2-
REF
W1
Y1
G
R
24V
24V(c)
Figure 3: TEC1101 Single-Stage, Factory-Set DIP Switch Settings and
Wiring Configuration
Setting the DIP
Switches

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls METASYS TEC1103 and is the answer not in the manual?

Johnson Controls METASYS TEC1103 Specifications

General IconGeneral
BrandJohnson Controls
ModelMETASYS TEC1103
CategoryThermostat
LanguageEnglish

Related product manuals