TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
21
For VSF control, the output is configurable for any range between 0 V and 10 V. The parameters are Start Voltage,
Full Speed Voltage, and Minimum Command. Start Voltage is the voltage output at which the fan begins running,
and Full Speed Voltage is the voltage output at which the fan reaches full speed. Minimum Command is the
percentage of the range between the Start Voltage and the Full Speed Voltage. The fan does not go below the
minimum command when the fan is turned on. By default, the Start Voltage is 2 V, the Full Speed Voltage is 10 V,
and the Minimum Command is 20%.
When the variable speed fan is off, the FAN binary output is off and the voltage at the VSF output is 0 V. When the
fan turns on, the FAN binary output turns on and the voltage at the VSF output begins controlling the fan. When the
VSF is configured for reverse acting mode (Start Voltage is above Full Speed Voltage), the VSF output goes to the
lesser of 10 V and 1 V above the Start Voltage when the fan is turned off.
To configure the variable speed parameters:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Start Voltage and adjust accordingly.
5. Press Full Speed Voltage and adjust accordingly.
6. Press Minimum Command and adjust accordingly.
7. Press to save and
to return to the previous screen.
Setting the Control Mode
The Control Mode informs the controller to run in Cooling only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and cooling setpoints. Control Mode does not override equipment
lockouts or changeover. To set the Control Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Control Mode and select Cooling, Heating, or Auto as desired.
5. Press to save and
to return to the previous screen.
Setting the Fan Mode - Fan Coil Only
The Fan Mode informs the controller how to handle the fan. There are two options for fan configuration: a Fan
Mode available to the installer through the menu system, and a fan override available as an option to the end user
from the Fan icon on the home screen. See Customizing the Home Screen
for information on enabling and
disabling end-user controls. The Fan Mode available to the installer is dependent on the fan type. The following
options are provided for single-and variable-speed fans:
On—Fan is continuously on
Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification modes
Smart—Fan cycles on demand with the controller entering cooling or heating modes during unoccupied
periods but is continuously running during occupied and standby periods
The following Fan Mode options are provided for multi-speed fans:
Low—Fan is continuously on low
Medium—Fan is continuously on medium

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3000 Series and is the answer not in the manual?

Johnson Controls TEC3000 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3000 Series
CategoryThermostat
LanguageEnglish

Related product manuals